红色主机5

 

The CK1000 is a 4-zone to 16-zone FACP (Fire Alarm Control Panel), which uses conventional input devices.  The panel accepts water flow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other normally-open contact devices. Outputs include four Notification Appliance Circuits (NAC, SOUND1-4), three standard Form-A relays (alarm, trouble and supervisory) and an EIA-485 port to interface with remote annunciators and optional remote relay modules. The FACP is field programmable via the panel keypad.  It also supervises all wiring, AC voltage and battery level.

 

This series of panels are basically the same in application and operation, their differences are shown in Table 1-1. CK1000 will be described as the example in the following sections.

 

Table 1-1

FACP

Number of Detection Zones

Number of Sounder Outputs

Output Delay Settings

CK1004

4

1

N/A

CK1008

8

2

N/A

CK1016

16

4

N/A

 

1.1 ProductFeatures

 

l      4,8,16 Class B Initiating Device Circuits (IDCs)

??1??7??1??77??1??7??1??77   All zones accept conventional detectors and any normally open contact device

l      Four Class B Notification Appliance Circuits (NACs)

l      One Form-A Alarm Relay

l      One Form-A Trouble Relay

l      One Form-A Supervisory Relay

l      3.0 amps of system power

l      Max 20 conventional detectors in one zone.

l      Auto/Manual mode setting enable walk test.

l      Each Zone can be disabled,

l      Sound output can be disabled.

l      Manual active sound output enabled.

l      Able to report short and broken circuit of detection zones.

l      Designed with standby batteries and space provision for two sealed lead-acid batteries.

l      Testing and disable functions.

 

AC Power

AC90-270 VAC, 50 Hz, 2.3 amps

Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation

Battery(lead acid only)

Maximum Charging Circuit: Normal Flat Charge—27.6V @ 0.8 amp

Maximum Charger Capacity: 18 Amp Hour batter

Sound Output Device Circuits

General Alarm Zones 1 through 16

Operation: All zones Class B

Normal Operating Voltage: Nominal 24 VDC (ripple = 100 mV maximum)

Alarm Current: 15 mA threshold

Short Circuit Current: 42 mA maximum

Maximum Loop Resistance: 100 ohms

End-of-Line Resistor: 4.7K, ½ watt

Detector Loop Current is sufficient to ensure operation of two alarmed detectors per zone

Standby Current: 7.26 mA

Three Relays Output

Relay contact rating: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30 VAC (resistive)

Nonresettable 24 VDC Power

Maximum ripple voltage: 10 mVRMS          Operating Voltage nominal 24 volts

Total DC current available from this output is up to 500 mA

Recommended maximum Standby current is 150 mA

 

1.3 Controls and Indicators

规格参数
型号 CK1008   继电器驱动 有  
探头输入方式 接线   品牌 安诺基  
供电电源 220   通讯方式 声光报警  
环境温度 -10-50   环境湿度≤ 90  
类型 消防报警主机   适用范围 家庭、工厂、宾馆 、酒店  
外形尺寸 0   颜色 白色  
包装参数
体积(m²)
产品重量(kg)
  • 与商品描述相符
  • 5
  • 5
  • 非常不满
  • 不满意
  • 一般
  • 满意
  • 非常满意
联系方式
注意:1 . 使用电话联系可有效保证您的号码隐私不被泄露
          2 . 拨打后可在后台进行拨打记录查询
          3 . 成交后在会员中心确认可获得积分
联系人:蔡玉
电话:18814452893
获取更低报价
联系电话:

按排行字母分类:A|B|C|D|E|F|G|H|I|J|K|L|M|N|O|P|Q|R|S|T|U|V|W|X|Y|Z

Copyright©2026 搜了网版权所有粤ICP备07509311号-1搜了网推广热线:400-888-5105 关注我们:

增值电信业务经营许可证:粤B2-20090212互联网药品信息服务资格证书:(粤)-非经营性-2012-0057 粤公网安备 44030502000007号